Protocol Plus Owner’s Manual OPERATION
Version 2 35
Copyright © 2010 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Controls response to loss of
power
Stop, Restart, Hold, Resume
time limit
Control aborts to Stopped
mode if power is lost for time
period longer then set value
start
enable
Allows mode to automatically
start when power is first
applied
Operating mode for powerup
start
Off, Manual, Timer, Pro-1 to Pro-8
Hysteresis for all alarms and
temperature events
1°C to 56°C (1°F to 100°F)
Process value for retransmit
output = 1VDC
-73°C to 760°C (-100°F to
1400°F)
Process value for retransmit
output = 5VDC
-73°C to 760°C (-100°F to
1400°F)
Time scale setting for program
and timer mode
7
Internal beeper sounds when
key is pressed
Internal beeper sounds at end
of cycle
Internal beeper sounds for
alarms
5.6.8. Setting up the Communication Page
The Communication Page contains parameters for the communications feature. Table 7
shows the menu items available.
5.6.8.1. Access Communication Page
1. Enter Setup Mode.
2. Press
Page until Communication displays.
3. Press Menu.
O
If the display does not change, the controller does not have the
communication board installed.
4. Change each parameter by pressing Menu until the desired parameter is displayed,
and then press ▲ or ▼ to change the value.
7
Power fail recovery time limit is always MM:SS regardless of time scale setting