* The Hardware Definition Code and input jumper configuration may need to be changed. See
Appendices A and B.
** If Remote Setpoint Input has been selected in the Hardware Definition Code, this parameter will
appear in the normal Program Mode parameter sequence. The upper display shows a product code
which defines the input range. The factory setting depends on code selected, see Appendix B.
*** An Alarm Hysteresis output is made active only when both alarms become active; it subsequently
becomes inactive only when both alarms are inactive. Thus, the status of an Alarm Hysteresis output
only when one alarm is active depends upon the alarm status immediately prior to that alarm being
activated.